TOOLS · TECHNICAL GUIDES · ELECTRICAL INFRASTRUCTUREWrite for us & partner ↗
Transformers · Worked example

Transformer Losses at 50% vs 80% Load: A Worked Comparison

A lower no-load loss does not guarantee lower total losses at every operating point. Compare two hypothetical transformers at 50% and 80% loading.

Power Infra Lab · Technical explainer · Updated October 8, 2026

At 50% loading, a transformer does not necessarily produce half its full-load losses. In the simplified model used here, its load-dependent component falls to one quarter, while no-load loss remains. At 80% loading, the load-dependent component is 64% of its rated value. That difference can reverse the result when comparing two designs.

The following figures are hypothetical, not product specifications or a claim that either loading level is optimal. They demonstrate how to use the transformer loss comparison calculator and how to document a result someone else can reproduce.

Use two loss inputs, not one efficiency headline

Let P0 mean no-load loss in kW, Pk mean the load-dependent loss measured at rated current in kW, and x mean the fraction of rated current. The screening formula is P_loss = P0 + Pk × x². Schneider Electric describes this relationship in its partial-load heat-loss explanation. The approximation holds the relevant test conditions fixed; it is not a thermal simulation.

For this exercise, both options have the same hypothetical 1,250 kVA rating and operating voltage. Their loss figures are assumed comparable at the same reference conditions. At 50% current loading, each carries approximately 625 kVA; at 80%, approximately 1,000 kVA. We compare equal delivered apparent load, not two differently sized transformers at the same percentage.

Assumed inputOption AOption B
No-load loss P01.10 kW1.70 kW
Rated load loss Pk9.00 kW7.00 kW
Energized annual hours8,7608,760
Energy-only tariff0.15 currency/kWh0.15 currency/kWh

At 50% load, Option A loses less

Enter 50 into the calculator’s load-percentage field, not 0.5. Internally, the model converts it to a fraction before squaring.

  • Option A: 1.10 + 9.00 × 0.50² = 3.35 kW.
  • Option B: 1.70 + 7.00 × 0.50² = 3.45 kW.
  • B minus A: 0.10 kW more loss.

If this operating point remained unchanged for all 8,760 hours, A would lose 29,346 kWh and B would lose 30,222 kWh. B therefore consumes 876 additional kWh for losses, costing 131.40 additional currency units at the assumed tariff. In the calculator’s savings convention, B versus A shows a negative saving of −131.40. The minus sign is meaningful, not an error.

At 80% load, the comparison reverses

Change only the loading field to 80%. Leave the ratings, loss inputs, hours and tariff unchanged.

  • Option A: 1.10 + 9.00 × 0.80² = 6.86 kW.
  • Option B: 1.70 + 7.00 × 0.80² = 6.18 kW.
  • A minus B: 0.68 kW less loss with B.

The annual loss-energy values are now 60,093.60 kWh for A and 54,136.80 kWh for B. Their difference is 5,956.80 kWh, or 893.52 currency units. B’s higher fixed loss is outweighed by its lower load-dependent loss at this operating point. This is an operating-energy result, not a purchase recommendation.

Find the crossover without guessing a best loading band

Set the two modelled loss expressions equal: 1.10 + 9x² = 1.70 + 7x². Rearranging gives 2x² = 0.60, so x = √0.30 = 0.5477, or about 54.77%. Below that loading, A has lower modelled losses; above it, B has lower losses. This crossover belongs to these two hypothetical input sets. It is neither a universal efficiency optimum nor an acceptable loading limit.

A varying load needs separate time blocks

Suppose A operates for 4,380 hours at 50% and another 4,380 hours at 80%. Its annual losses are 3.35 × 4,380 + 6.86 × 4,380 = 44,719.80 kWh. The average loading is 65%, but using a constant 65% produces (1.10 + 9 × 0.65²) × 8,760 = 42,945.90 kWh. That shortcut understates this scenario by 1,773.90 kWh.

The reason is visible in the arithmetic: the average of 0.50² and 0.80² is 0.445, whereas 0.65² is 0.4225. For a multi-period profile, run each period separately and sum its loss energy. The website’s worksheet uses one constant operating point per run; it does not ingest an hourly load series.

What to record before comparing real equipment

Ask for the exact product configuration and separate loss figures. Schneider Electric’s dry-type transformer loss-data guidance notes that current loss information may need to be requested from product support. Do not mistake total full-load loss for the Pk input: adding P0 to that total would count the no-load component twice.

  • Record ratings, voltage, frequency, reference temperature and the source document date.
  • Keep energized hours separate from hours with useful output; an energized idle period still belongs in this model.
  • For unequal ratings, establish the same served load and calculate each option’s loading fraction separately.
  • Identify omitted temperature changes, harmonics and auxiliary cooling; verify their treatment with the manufacturer.

Energy-only savings exclude purchase price, financing, maintenance and demand charges. Use this comparison to make assumptions explicit, then combine it with the transformer sizing framework and project-specific engineering review. A precise annual number is useful only when the loading history and loss inputs justify it.

Sources & further reading

  1. Schneider Electric: Liquid-filled transformer heat loss at percentage loads ↗
  2. Schneider Electric: Obtaining low-voltage dry-type transformer loss data ↗

Sources checked October 8, 2026. Examples are hypothetical unless explicitly identified as published product data.

Educational planning only. These tools do not replace a licensed professional’s design, a manufacturer selection study or applicable local requirements.