TOOLS · TECHNICAL GUIDES · ELECTRICAL INFRASTRUCTUREWrite for us & partner ↗
Comparison worksheet

Compare transformer losses on the same basis.

Enter values from two actual data sheets. This is not a brand ranking or a full ownership-cost model.

Option A

Option B

Initial values are hypothetical examples, not manufacturer specifications.

The model

Loss kW ≈ no-load loss + rated load loss × (load % ÷ 100)²
Annual loss energy ≈ loss kW × energized hours

This model assumes a constant load during energized hours. Do not square an annual-average load to estimate losses for a varying load profile.

The simple square-law approximation omits temperature variation, changing daily load, harmonics, auxiliary cooling power, purchase price, maintenance and financing. Match the data-sheet test conditions and ratings before comparing options.