UPS Battery Energy & Runtime Estimator

Estimate an energy-balance runtime from usable battery energy and conversion efficiency.

Interactive calculator · explicit assumptions

UPS Battery Energy & Runtime Estimator

Calculations run in your browser. Sharing puts numeric assumptions in the link. No registration required.

Formula

Runtime minutes = nominal kWh × (usable % ÷ 100) × (efficiency % ÷ 100) ÷ load kW × 60.

Worked example

100 kWh, 80% usable energy and 94% efficiency supplying 100 kW gives 45.12 minutes in this simplified model.

What this calculation does not cover

An energy estimate, not a manufacturer discharge curve. It excludes discharge-rate effects, temperature, aging, inverter power limits and minimum DC voltage. Check actual runtime curves for procurement or safety decisions.